This study employs Computational Fluid Dynamics (CFD) numerical simulation methods using FLUENT software to investigate the transport and elimination characteristics of Sulfur Hexafluoride (SF6) during accidental leakage in a Gas-Insulated Transmission Line (GIL) cable tunnel. The research compares two ventilation modes—axial fans and jet fans—and explores the effects of exhaust port parameters on SF6 capture performance. A typical tunnel section, measuring 1 600 m in length, 13.5 m in inner width, and 8 m in total height, was modeled, containing 18 GIL pipelines with a diameter of 512 mm. The simulations utilized the RNG k–ε turbulence model coupled with the species transport equation. To simulate a severe single-compartment incident, the leakage source was positioned 50 m from the tunnel entrance above the central GIL pipeline, with an SF6 mass flow rate of 5.76 kg/s maintained for 300 s. Under equivalent conditions of a 5 m/s average wind speed across the cross-section, the performance of axial and jet fan ventilation modes was compared, along with a detailed analysis of exhaust port parameter configurations. The results indicate that the stratified flow field produced by jet fans, characterized by high velocity in the upper region and low velocity near the bottom, effectively suppresses the upward diffusion of SF6 toward the breathing zone. Compared to axial ventilation, jet fans reduced the peak SF6 volume fraction in the breathing zone from approximately 21 000 μL/L to around 8 500 μL/L, representing a reduction of about 60%. Additionally, the longitudinal spread distance L1000 decreased by approximately 17% relative to the axial fan mode. Given their organizational flexibility and the benefits of segmented relay ventilation, jet fans are deemed more suitable for meeting emergency ventilation requirements in ultra-long GIL cable tunnels. The layout parameters of the exhaust ports play distinct roles in SF6 elimination performance: the total extraction area and negative pressure are crucial for determining the overall capture amount, while the degree of spatial concentration influences the effectiveness of spread control. A decentralized layout fails to inhibit SF6 migration; under operating conditions B1, B2, and B3, the maximum spread distance exceeded 900 m during the leakage period. In contrast, a centralized layout effectively blocks SF6 migration, limiting the maximum spread distance to approximately 350 m under conditions B4, B5, and B6—about 61% shorter than that observed with the decentralized layout. Furthermore, maintaining a constant total exhaust area and negative pressure, reducing the port spacing from 125 m to 50 m can further limit the spread distance by approximately 50%.
[1] 高凯, 李莉华. 气体绝缘输电线路技术及其应用[J]. 中国电力, 2007, 40(1): 84–88.
[2] 王一鹏, 梁丁丁, 石磊, 等. 基于CFD的SF_(6)气体绝缘设备泄漏模拟及防护措施[J]. 安防技术, 2017, 5(2): 15–21.
[3] Morton B R, Taylor G I, Turner J S. Turbulent gravitational convection from maintained and instantaneous sources[J]. Proceedings of the Royal Society of London. Series A, Mathematical and Physical Sciences, 1956, 234(1196): 1–23.
[4] Ricciardi L, Prévost C, Bouilloux L, et al. Experimental and numerical study of heavy gas dispersion in a ventilated room[J]. Journal of Hazardous Materials, 2008, 152(2): 493–505.
[5] Deaves D, Gilham S, Spencer H. Mitigation of dense gas releases in buildings: use of simple models[J]. Journal of Hazardous Materials, 2000, 71(1/2/3): 129–157.
[6] Kunsch J P, Webber D M. Simple box model for dense-gas dispersion in a straight sloping channel[J]. Journal of Hazardous Materials, 2000, 75(1): 29–46.
[7] 关为民, 卞超, 谭婷月, 等. 苏通GIL综合管廊SF_(6)气体泄漏分布特性数值模拟研究[J]. 高压电器, 2020, 56(11): 102–110.
[8] 肖国锋, 何娜萍. 泄漏孔径对特高压GIL管SF_(6)泄漏影响的混合数值模拟[J]. 南方能源建设, 2021, 8(1): 115–121.
[9] 徐亮, 张高爽, 龙艳, 等. 特高压管廊GIL热特性的数值模拟[J]. 哈尔滨工业大学学报, 2018, 50(7): 177–184.
[10] 徐大坤, 王浩, 姜洋彬, 等. GIL管廊热环境及外逸气体浓度的分析[J]. 安全与环境学报, 2024, 24(12): 4695–4704.
[11] 陈邦国, 李峰, 赵文彬. GIL廊道内SF_(6)气体泄漏扩散及风机安装优化研究[J]. 水电能源科学, 2020, 38(6): 177–180, 168.
[12] 孙岗, 李浩翥, 张鹏飞, 等. 苏通GIL综合管廊SF_(6)气体排除方案研究[J]. 电力勘测设计, 2020(10): 66–70.
[13] 隋心, 张正维, 闵绚, 等. 超长GIL综合管廊SF_(6)气体泄漏模拟研究[J]. 现代隧道技术, 2020, 57(3): 91–98, 107.
[14] 徐长福, 赵新冬, 梁伟, 等. 基于数字孪生技术的GIL综合管廊气体泄漏与排除全过程风险性评估[J]. 电力系统保护与控制, 2025, 53(3): 160–171.
[15] Yakhot V, Orszag S A. Renormalization group analysis of turbulence. I. Basic theory[J]. Journal of Scientific Computing, 1986, 1(1): 3–51.
[16] GB 50838—2015 城市综合管廊工程技术规范[S].
[17] 胡康, 邵雪. 基于CFD对公路隧道纵向射流通风系统的研究[J]. 南方能源建设, 2020, 7(增刊2): 131–136.
[18] Galdo Vega M, Argüelles Díaz K M, Fernández Oro J M, et al. Numerical 3D simulation of a longitudinal ventilation system: memorial tunnel case[J]. Tunnelling and Underground Space Technology, 2008, 23(5): 539–551.
[19] GB 26860—2011 电力安全工作规程 发电厂和变电站电气部分[S].
Basic Information:
DOI:10.13637/j.issn.1009-6094.2026.0677
China Classification Code:TM75
Citation Information:
[1]Zhong Ke,Chen Wangyu,Li He ,et al.SF_(6) leakage characteristics and exhaust port layout in GIL tunnels under axial and jet ventilation[J].Journal of Safety and Environment().DOI:10.13637/j.issn.1009-6094.2026.0677.
Fund Information:
国网上海市电力公司举手制项目(B30931240005);国网上海市电力公司群众性创新科技项目(520931250007)
2026-09-14
2026-09-14
2026-09-14